We have established ourselves as a quality focused organization engaged in manufacturing and supplying Electrical Constant Voltage Transformers. These transformers are manufactured in compliance with set industrial norms, using high quality materials and components. To provide the best range, we check these transformers on efficiency and performance parameters. We make these Electrical Constant Voltage Transformers available for clients in different technical specifications as per their requirements.
Key Features:
General Technical Specifications of our Ferro Resonant Transformer (CVT)
Input Voltage | 180 V 260 V AC |
Line Frequency | 50 Hz |
Output Voltage | 220 230 V 1% |
Output Step Load Response | 2 cycles (30 to 40 milliseconds) |
Efficiency | 90% (approx) under full load conditions |
Output Wave Form | Sinewave |
Wave from Distortion | 5% (approx) under full load conditions |
Load power Factor | 0.75% lag to 0.9% lead |
Ambient Temperature | -10C to 50C |
Transformer Type | Ferro-Resonant |